How to Insulate a Floor: A Guide to Thermal, Sound and Water Insulation

Cover titled Floor Insulation, showing the MegaUsta mascot with XPS boards, a stone wool floating floor board and an EPS underfloor heating board

In short: Floor insulation is insulation placed between the layers of a floor to limit the passage of heat, sound or water through it. In a ground-bearing floor thermal insulation and waterproofing come to the fore, in an intermediate floor impact sound insulation and in a wet area waterproofing. The material and thickness are chosen according to what lies beneath the slab.

This guide explains which insulation is needed for each type of floor, the order of the layers and the choice of board. For the insulation work in the whole building see our guide to building insulation, and for walls our guide to wall insulation.

What is floor insulation and which floors is it applied to?

Floor insulation is not a single application: thermal, sound and water insulation are dealt with separately depending on whether there is ground, an unheated space or another dwelling beneath the slab. According to İZODER, thermal insulation is also applied to floors that separate dwellings from the ground or from spaces that are not lived in.

Type of floor What lies beneath? Main insulation Mega product Detailed guide
Ground-bearing slab Ground Thermal and water XPS smooth board; Fullback Duo (not planned as the main waterproofing on a horizontal surface exposed to water under pressure) foundation and basement wall insulation
Floor above an unheated space or an open passage Basement, garage or outside air Thermal XPS smooth board; Floating Floor Board in a floor over an open passage thermal insulation materials
Intermediate floor Another dwelling Impact sound; thermal resistance of at least 0.80 m²K/W Floating Floor Board (MEGA SW FF100/110/120) what is a floating floor
Floor with underfloor heating Varies Thermal insulation beneath the pipes EPS underfloor heating board; XPS or EPS board beneath it underfloor heating insulation
Wet area and balcony floor Varies Water Fullback Duo bathroom waterproofing

Source: Regulation on Energy Performance of Buildings, Article 9; Regulation on Waterproofing in Buildings; Regulation on the Protection of Buildings against Noise; Mega product pages. The table is general guidance.

How are thermal insulation and waterproofing done in a ground-bearing floor?

In a ground-bearing floor, waterproofing is done first and thermal insulation second; screed and flooring go on top of the thermal insulation board. The Regulation on Waterproofing in Buildings covers the foundations, floors and basement walls of new buildings that are in contact with the ground; thickness and consumption are shown in the design details.

  1. Establish the water condition. The regulation has waterproofing designed against water under pressure or without pressure according to the permeability in the ground investigation and the groundwater level. On horizontal surfaces exposed to water under pressure, sheet-type material is the rule.
  2. Carry out the waterproofing. In a raft foundation the base waterproofing is done on the blinding concrete, before the foundation concrete is poured. Waterproofing is applied from the side of the building element that is exposed to water.
  3. Lay the thermal insulation board. After the waterproofing has been covered with protective concrete and the foundation concrete has been poured, boards of the calculated thickness are laid on that concrete with staggered joints and without gaps. If the design places the thermal insulation beneath the foundation, the board carries the load of the building continuously; its type is determined in the structural design.
  4. Pour the screed and lay the flooring. A separating layer is laid over the boards and an edge strip is placed along the walls; the screed is poured on top, and the flooring is laid after the screed has dried.

In this floor the board takes both load and moisture; this is why XPS stands out with its low water absorption and high compressive strength. The product page of Mega XPS smooth board lists insulation of foundations in contact with the ground, floors and under parquet, and underfloor heating among its areas of use. The thickness of the thermal insulation is determined in the thermal insulation design: in the TS 825 calculation, floors in contact with the ground or with outside air are also treated as part of the building envelope.

House drawn with a section through the ground, the base of the foundation and the flat roof of the glazed extension marked in red and the below-grade basement walls in red hatching; in front, blue Mega XPS boards and an XPS pack
Surfaces in contact with the ground: the red area shows the base of the foundation and the hatched areas the below-grade basement walls.

Which board is used for thermal insulation in floors?

In a floor the board is chosen according to the load it will carry and the moisture condition: XPS in floors in contact with the ground or at risk of moisture, EPS in dry intermediate floors, and the stone wool floating floor board in intermediate floors where impact sound is to be reduced as well.

Board (Mega type) Material λD (W/mK) Compressive strength at 10% deformation Long-term water absorption Thickness
MEGA XPS T1500 XPS 0.035 150 kPa ≤0.7% (total immersion) 20–80 mm
MEGA XPS T3000 XPS 0.035 300 kPa ≤0.7% (total immersion) 20–120 mm
EPS 100W White EPS 0.036 100 kPa ≤3% (total immersion) 10–100 mm
EPS 120W White EPS 0.034 120 kPa ≤2% (total immersion) 10–100 mm
MEGA SW FF100/110/120 (Floating Floor Board) Stone wool ≤0.036 25 kPa ≤3 kg/m² (partial immersion) 30 mm

Source: Mega technical data sheets. The reaction-to-fire class is E for the XPS and EPS boards and A1 for the stone wool board (TS EN 13501-1).

We explained how the compressive strength class is chosen in our article on XPS compressive strength and the difference between the two foam materials in XPS or EPS.

How is sound insulation done in an intermediate floor?

Sound insulation in an intermediate floor is done with a floating floor: the screed and flooring rest on a resilient insulation board and are not rigidly connected to the walls at any point. The aim is to reduce the passage of impact sounds such as footsteps to the storey below.

  1. Prepare the structural slab. The surface must be clean, dry and flat; rubble and lumps of mortar crush the board at points.
  2. Place the edge strip. The strip is placed around the walls, columns and vertical pipes, high enough to pass the top level of the screed and flooring.
  3. Lay the insulation boards. The boards are butted tightly together; no gaps are left at the joints.
  4. Cover with the separating layer. Polyethylene sheet is laid with overlaps and turned up at the edges; it prevents the screed mortar from seeping into the board joints.
  5. Pour the screed. The screed is poured as a continuous slab and does not touch a wall, column or pipe.
  6. Lay the flooring and trim the strip afterwards. The projecting part of the edge strip is cut after the flooring and joints are finished.

The Regulation on the Protection of Buildings against Noise assesses the impact sound insulation of floors with the indicator L’nT,w and requires at least acoustic performance class C in new buildings. According to its technical data sheet, Mega’s stone wool Floating Floor Board has a density of 100–120 kg/m³, measures 1200 x 600 mm and is 30 mm thick; the thermal resistance in the data sheet is 0.80 m²K/W.

The intermediate floor is also subject to a thermal requirement: the Regulation on Energy Performance of Buildings requires a thermal resistance of at least 0.80 m²K/W between independent units. The total thermal resistance of the floor is calculated in the design together with all the layers. The details of the system are in our article what is a floating floor.

Two-storey house drawn in section with the floor between the two storeys marked by a red line; in front, stone wool boards and Mega StoneWool packs
Sound insulation in an intermediate floor: the red line shows the position of the stone wool floating floor board under the screed.

How is insulation built up in a floor with underfloor heating?

In a floor with underfloor heating the insulation is built up beneath the pipes: from bottom to top the order is structural slab, thermal insulation board, heating board that holds the pipes, pipes, screed and flooring. To these are added the edge strip along the walls and, in a floor in contact with the ground, the waterproofing done before the insulation boards. The insulation beneath limits the heat produced from escaping into the concrete slab and the space below.

Planning guides based on EN 1264-4 give minimum thermal resistance values for the insulation beneath the heating layer according to the condition beneath the slab:

Condition beneath the slab Minimum thermal resistance (m²K/W)
A heated room 0.75
An unheated or intermittently heated room, the ground, or outside air with a design temperature above 0 °C 1.25
Outside air, design temperature between 0 °C and -5 °C 1.50
Outside air, design temperature between -5 °C and -15 °C 2.00

Source: system guide based on EN 1264-4. The values are lower limits; where the groundwater level is closer than 5 m, the guide recommends increasing the value given for a ground-bearing floor. In a floor between independent units, the requirement of at least 0.80 m²K/W in the Regulation on Energy Performance of Buildings also applies. The final thickness is determined in the thermal insulation design.

As described on its product page, Mega’s EPS underfloor heating board fixes the hot water pipes to the floor in an even layout. In the insulation calculation, XPS or EPS boards whose thermal conductivity and compressive strength are documented in a technical data sheet are taken as the main layer. The details of the layers and the common mistakes are in our guide to underfloor heating insulation.

Section of a room with heating pipes running over red boards laid on the floor, covered by screed and flooring; beside it, a white studded EPS underfloor heating board
A floor with underfloor heating: the red area shows the EPS underfloor heating board that holds the pipes; screed and flooring go on top.

How is waterproofing done in wet area and balcony floors?

In wet area and balcony floors the waterproofing is done before the tiling, on a prepared surface. The Regulation on Waterproofing in Buildings covers the balconies and wet areas of new buildings and requires the material to be chosen according to the water action.

  • Surface preparation: The surface to be waterproofed is cleared of anything that reduces adhesion, such as dust, loose fill, paint and formwork oil.
  • Details: At floor-wall junctions, service penetrations and movement joints, additional measures are taken with products that complete the seal.
  • Compatibility: Mutually compatible system components are used in waterproofing details.

According to its product page, Mega’s cement and acrylic based, two-component Fullback Duo product is used in wet areas, balconies and small terraces. You can find the order of application in our articles on bathroom waterproofing and balcony waterproofing, and the material groups in our guide to waterproofing materials.

Can an existing floor be insulated afterwards?

Yes, but the scope is determined by whether the floor can be taken up. The layer under the screed cannot be reached after the building is finished without removal work; this is why the most comprehensive solution is applied when the floor is being renewed.

  • If the floor is being renewed: The old flooring and screed are removed and a floating floor is built, or a thermal insulation board is added under the screed. Because the floor level will rise, door clearances, thresholds and wet area entrances are worked out beforehand.
  • If the screed cannot be removed: A resilient underlay that reduces impact sound is placed under the flooring; the flooring is still kept clear of the wall.
  • In the short term: Carpets, thick rugs and felt pads fitted to furniture feet reduce footstep and dragging noise at source.

If there is damp or mould in the floor, its source is identified first; we explained the problems in basement storeys in our article on basement damp problems.

What are the common mistakes in floor insulation?

Most mistakes stem from edge details, the wrong choice of board and confusing the order of the layers.

  • Not fitting the edge strip, or cutting it below the screed level. If the screed touches the wall, a sound bridge forms.
  • Skipping the separating layer. Mortar seeps into the board joints and ties the screed to the structural slab.
  • Choosing a board for a load-bearing floor without looking at its compressive strength, or comparing the kPa value in the data sheet directly with the load. That value is the stress at 10% deformation in a short-term test; the stress allowed under sustained load is lower and is calculated in the design.
  • Treating thermal insulation as a substitute for waterproofing in a ground-bearing floor. A thermal insulation board does not take the place of waterproofing.
  • Leaving the floor-wall junction and service penetrations in a wet area without detailing.
  • Choosing the thickness without calculation. The thickness of thermal insulation is determined in the thermal insulation design.

Application note from MegaUsta: Photograph the floor before pouring the screed: is the edge strip continuous, are the board joints closed, is the separating sheet turned up at the edges? Once the screed is poured these layers cannot be seen.

Frequently Asked Questions

How is a floor insulated?

A floor is insulated layer by layer according to what lies beneath the slab. In a ground-bearing slab, waterproofing comes first, then the thermal insulation board, with screed and flooring on top. In an intermediate floor, a resilient board that cuts impact sound is laid under the screed and the screed is separated from the walls by an edge strip. In a wet area the waterproofing is done before the tiling. The thicknesses are determined in the design.

Which material is used for floor insulation?

XPS board is used in ground-bearing, load-bearing floors; in Mega’s data sheets the compressive strength at 10% deformation is between 150 and 300 kPa depending on the type and the long-term water absorption no more than 0.7%. The kPa value in the data sheet is not a design load; in a floor under sustained load the type is chosen in the design. In an intermediate floor the stone wool floating floor board is laid under the screed. In underfloor heating the pipes are held by the EPS underfloor heating board. For waterproofing bathroom and balcony floors, cement-based two-component liquid-applied materials are used.

How thick should floor insulation be?

The thickness of the thermal insulation is calculated in the thermal insulation design prepared in accordance with TS 825; the condition beneath the slab and the λD value of the board determine the result. Thermal resistance is found by dividing the thickness by the λD value: for MEGA XPS T3000 board with a λD of 0.035 W/mK, 50 mm gives about 1.43 m²K/W by calculation; the value declared in the data sheet is 1.40 m²K/W. The stone wool floating floor board is offered at a thickness of 30 mm and the thermal resistance in its data sheet is 0.80 m²K/W.

What is done to the floor to stop sound reaching the storey below?

Against impact sounds such as footsteps, the floor is built as a floating floor: a resilient insulation board is laid under the screed, and the screed is separated from the walls, columns and pipes by an edge strip. If the screed touches the wall at a single point, a sound bridge forms. If the screed cannot be removed, a resilient underlay that reduces impact sound is placed under the flooring; carpets and felt pads under furniture also reduce the sound at source.

Why is a ground-floor slab cold?

Because beneath the slab there is ground, an unheated basement or outside air, and heat escapes in that direction. According to İZODER, thermal insulation is also applied to floors that separate dwellings from the ground or from spaces that are not lived in. In a new building the insulation of this floor is calculated in the thermal insulation design. In an existing building a thermal insulation board can be added under the screed when the floor is renewed; because the floor level will rise, door clearances are worked out beforehand.

Can thermal insulation be installed under parquet?

Yes. The product page of Mega XPS smooth board lists floors and under parquet among its areas of use; the technical data sheet also includes an under-parquet surface option. The board is chosen by its compressive strength so that it is not crushed under load. If the aim in an intermediate floor is to reduce footstep noise, the screed under the parquet is built as a floating floor or a resilient underlay is placed under the flooring.

Sources

You can review the product groups offered for floors on our insulation products page and contact us through our contact page with questions about your project.

General Directorate
Factory